*5283The group start consists of an application corresponding to that in the manual for the
functional unit GROUP. The group start contains eight steps. The logic for control and
presentation contains around 70 PC elements. Subordinated functional units of the type
MOTCON are not included in this figure.
6(4 The sequence is assumed to consist of a sequence head, 10 steps and one data base
element SEQ.
7(;7Consists of one data base element TEXT.
7DEOHKDQGOLQJ The figures are calculated for one table with 10 rows and 100 values per row.
0DVWHU9LHZThe displays are assumed to have 40 text strings with 20 characters and 30
dynamic values. The event list is assumed to accommodate 100 events.
&HQWUDORSHUDWRUVWDWLRQThe numbers for logs are based on a log with 10 variables each with
240 stored values. Each value takes approximately 5 bytes.
Each group member in the group alarm function is assumed to be included in three group alarm
objects.
0DVWHU%DW FKThe number for PROCESSES is based on 50 storage vessels, four sections
and 20 operations with six recipe variables each.
6SDFHIRUVWRUDJHRI8VHU'LVNHWWHFRQWHQW Included only if you choose the user diskette as a
backup option in Advant Controller 450. The memory space can be dimensioned.
100 kByte is a space suitable for most requirements.
6SDUH5$0DUHD Reserve RAM capacity is required because information about memory
requirements of the different functions is generalized and inherently uncertain. This RAM
compensates for minor departures from the data constituting the basis of the memory
requirement presented. Extra memory is also required when commissioning to permit smaller
adjustments of the application program.
7RWDO5$0UHTXLUHP HQW Must be less than the RAM size of the processor module.
7DEOH &DOFXODWLRQRI5$0UHTXLUHPHQW
2EMHFWW\SH 5HPDUN 7RWDO
)DFWRU
NE\WHV
5$0UHT
AI/AO signals S100 I/O x 0.30
S400 I/O (MP 51 not included) x 0.30
S800 I/O x 0.27
DI/DO signals S100 I/O x 0.26
S400 I/O (MP 51 not included) x 0.26
S800 I/O x 0.14
S800 I/O station No. of S800 I/O stations on AF 100 x 0.40
Calculated signals For presentation and event handling in
AS 500 Series operator stations (includ-
ing signals via Advant Fieldbus 100)
x 0.30