Advant
®
Controller 450 User’s Guide
Chapter 2 Installation
2-14 3BSE 002 415R701 Rev A
degree of interference (for example electromagnetic relays with no interference suppression).
Consider this when you are ordering the equipment.
To ensure adequate ventilation, there should be a free space, 150 mm high, between the top of
the cabinet and the ceiling or the underside of any beam, duct or similar structure over the
cabinet. When cables enter the cabinet from above, the space available should be at least
1000 mm high to provide working space.
The distance between the rear and the sides of the cabinet and an adjacent wall shall be no less
than 40 mm. This also ensures good ventilation.
If hinged frames or front doors of end cabinets are to open fully without touching adjacent
walls, increase the distance as follows:
At hinged side of hinged frame
cabinet RM500V1 - 300 mm (11.8”)
cabinet RM500V2 - 350 mm (13.8”).
At hinged side of single door cabinet
cabinet RM500V1 - 760 mm (29.9”)
cabinet RM500V2 - 660 mm (26.0”).
At hinged side of double door cabinet
cabinet RM500V1 - 382 mm (15.0”).
Figure 2-6. Minimum Distance to the Walls and the Ceiling

Table of Contents

Other manuals for ABB Advant Controller 450

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB Advant Controller 450 and is the answer not in the manual?

ABB Advant Controller 450 Specifications

General IconGeneral
BrandABB
ModelAdvant Controller 450
CategoryController
LanguageEnglish

Related product manuals