Advant
®
Controller 450 User’s Guide
Appendix H Halt Codes
H-2 3BSE 002 415R701 Rev A
NOTE
In all situations when the controller has stopped you should carefully read all
halt codes and system messages available before you proceed. See Section
5.4.2.1, Reading of System Messages.
Table H-1. List of Halt Codes
Halt
Code
Significance Corrective Actions
-3. Backup CPU in a redundant pair stopped when
restarted
1. Check the mode switches on primary and backup
CPU boards. Restart the backup CPU with the
mode switch in the same position as the primary
CPU had when it was last restarted.
NOTE
If position “AUTO” does not work then
switch to “CLEAR” or vice versa.
2. Check size of primary memory on primary and
backup CPU boards (8/16 MByte). Make sure
they are equal and restart the backup (or the
system).
00 Debug trap in system mode The halt codes 0 - 5 do not normally appear in a
system after commissioning but if one should appear,
it is probably due to interference, program error or
special hardware fault.
01 Fault in system mode (probably memory or bus
fault)
02 Fault in system mode (probably memory or bus
fault)
03 RAM fully occupied
04 Addressing error in system mode
05 Bus fault in system mode (e.g. impermissible
board extraction or memory error)
07 Memory error. RAM test. Replace the processor module

Table of Contents

Other manuals for ABB Advant Controller 450

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB Advant Controller 450 and is the answer not in the manual?

ABB Advant Controller 450 Specifications

General IconGeneral
BrandABB
ModelAdvant Controller 450
CategoryController
LanguageEnglish

Related product manuals