Advant
®
Controller 450 User’s Guide
Chapter 5 Maintenance
5-34 3BSE 002 415R701 Rev A
5.5.3 Fault Finding Principles
Introduction
Perform fault finding in a systematic and logical manner.
You must make a distinction between a system which has been in operation and a system which
has not been operated previously. In the latter case, always check the following indications first,
if relevant:
The cabinet has mains voltage connected
All circuit boards are plugged in correctly
All connections are made correctly
All boards are jumpered correctly.
If these checks do not correct the malfunction, continue with the procedures described below.
Fault Finding Principles
You are notified of a fault in one or several ways, as described in Section 5.5.2, Diagnostics and
Fault Announcement.
Three main “gateways” to the source of failure can be distinguished. Figure 5-14 illustrates the
notification of faults and the principles for fault finding.
If a central operator station is available, you should especially watch for opportunities to point
out a faulty replaceable unit outgoing from a system message and information given in the
system status displays. See Section 5.5.2.1, System Status and Plain Language System
Messages. You can treat most fault finding then, in principle, as indicated under the heading
Typical Simple Scenario below.
In a more complicated situation, other measures are applicable.
See A Complex Scenario below.
The concept of FDS and LDS in Figure 5-14 represents different qualities of diagnostics
support:
FDS - Full Diagnostics Support
A faulty unit/function is pointed out.
LDS - Limited Diagnostics Support
A complex indication exists which warrants further manual fault finding.
With respect to the necessary outfit when fault finding and, to a certain degree, the need for
skilled personnel, there is a division in basic and advanced fault finding.
Basic fault finding with full diagnostics support is covered by this Users Guide. Advanced fault
finding with limited diagnostics support is only briefly dealt with here.
Advanced fault finding presume practical knowledge in fault finding. Training courses are
arranged by
Automation University Sweden, Training Center.

Table of Contents

Other manuals for ABB Advant Controller 450

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB Advant Controller 450 and is the answer not in the manual?

ABB Advant Controller 450 Specifications

General IconGeneral
BrandABB
ModelAdvant Controller 450
CategoryController
LanguageEnglish

Related product manuals