Advant
®
Controller 450 User’s Guide
Section 2.4.2 Controller and I/O
3BSE 002 415R701 Rev A 2-65
2.4.2.7 Summary of the Controller Start-up and Verification of the Start
The following summary is a basic “from scratch” step-by-step instruction explaining how to
start up. Other working schedules exist, especially in connection to revisions and system
enlargement. Please refer to the reference manual AMPL Configuration Advant Controller 400
Series for complete information.
1. Power up
Set start mode to 3 (CLEAR) on processor module
Set power switch on
For indications which verify a successful power-up, see Section 2.4.2.1, Power-up.
2. Working mode CONFIGURATION
Automatically enter the working mode CONFIGURATION at power-up
Then set start mode selector in position 1 (AUTO). No ENTER
Processor module indicates P2 (working mode CONFIGURATION).
3. Controller system configuration
a. Dimensioning of data base, DIMDB
b. Creating the data base, CRDB
c. Data entry of data base, MDB
d. Dumping and loading (compress) the data base, DUTDB/LOTDB
e. Dimensioning of PC program tables, DIMPC (have to be done to enable update of
I/O signals).
4. Configuration/application building
a. Populating the data base, MDB
b. Entering and editing PC program, miscellaneous commands
c. Dumping and loading PC programs, DUTPT/LOTPT.
5. Backup of the entire RAM, DUAP.
6. Disabling working mode CONFIGURATION, DICONFIG.
In addition to those indications obtained at power-up:
All red LED F (Fault) on S100 I/O board fronts are switched off.
The yellow LEDs INIT and INHIB on S100 I/O Bus Extenders DSBC 174/
DSBC 176 board front are switched off.
The processor module changes over and indicates P1 (working mode OPERATION).
The system is now started and ready for operation.
Perform the final stages, which include start of application program execution, successively and
relate to the product verification. One PC program at a time.
WARNING
When the application program is started, the process to be controlled is
influenced.

Table of Contents

Other manuals for ABB Advant Controller 450

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB Advant Controller 450 and is the answer not in the manual?

ABB Advant Controller 450 Specifications

General IconGeneral
BrandABB
ModelAdvant Controller 450
CategoryController
LanguageEnglish

Related product manuals