EasyManuals Logo
Home>ABB>Controller>Advant Controller 450

ABB Advant Controller 450 User Manual

ABB Advant Controller 450
564 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #265 background imageLoading...
Page #265 background image
$GYDQW
&RQWUROOHU8VHU¶V*XLGH
6HFWLRQ 3URFHVV,QWHUIDFH
3BSE 002 415R701 Rev A 3-19
DSTD 108LP
Same as DSTD 108P but for maximum load current on it is 200 mA.
DSTD 109P
Connection unit with eight static outputs, 24 V 2 A with common power supply.
Each connection unit (DSTD 109P) is 120 mm long. With pluggable screw terminals.
DSDO 120
DSTD120A, DSTK 220L3.2
Static outputs for 24 V - 48 V d.c. (transistor outputs). The board is designed to withstand a load
up to 1 A per channel. The supply is divided in the connection unit into two groups of eight
channels each. Each has a common supply and 0V. The outputs are galvanically isolated from
the internal electronics.
*XLGHOLQHV3XOVH&RXQWLQJDQG3RVLWLRQLQJ%RDUGV
DSDP 140A
DSTD 150A/DSTD 190, DSTK 225SL3
A positioning loop for positioning up to 80 kHz.
DSDP 150
DSTD 150A/DSTD 190, DSTK 225SL3
Twelve channels 5/12/24 V d.c. for pulse and frequency measurement up to a maximum of
10 kHz. Pulse or frequency measurement is selected optionally for each channel pair. To obtain
acceptable accuracy, the frequencies which the two channels in a channel pair are to measure
should be fairly similar.
DSDP 170
DSTX 170, DSTK 228L3
Four channel high-speed pulse counter board for up to 2.5 MHz. The board is primarily
intended for control of motor operation where there is a need for position/length and
speed/frequency measuring.
*XLGHOLQHV&RQQHFWLRQRI6WDWLF&RQYHUWHUV
DSDC 111
DSTX 110, DSTK 224L3
A board to connect a thyristor converter with analog control of d.c. motor operation.
 6,26\VWHP
*XLGHOLQHV$QDORJ,QSXWVDQG2XWSXWV
With current signals and series coupling of loads, the total resistance may not exceed the
resistance through which the sensor output can be driven.
The referred type designations below are valid for S400 I/O Units.
DSAX 452
This is a combination unit for 14 analog inputs and 6 analog outputs for applications which
require considerable accuracy. You can ground the transducer and load if the difference in
potential between the load ground and the DSAX 452 ground is within the specification.
The equivalent resistance caused by the ground voltage drop and the load resistance concerned
together is not to exceed 650 with a current signal, 20 mA.

Table of Contents

Other manuals for ABB Advant Controller 450

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB Advant Controller 450 and is the answer not in the manual?

ABB Advant Controller 450 Specifications

General IconGeneral
BrandABB
ModelAdvant Controller 450
CategoryController
LanguageEnglish

Related product manuals