3-60 3BSE 002 415R701 Rev A
3RZHU6XSSO\
Current consumption is a complex matter when it comes to a flexible control system concept.
For rules for calculation of current consumption and dimensioning of distribution board fusing,
see Section 3.1.3, Power Supply.
A quick guide of power consumption to use in a very preliminary phase of work on a project or
anytime you need estimated figures for planning purposes follows.
Note that average figures are given. That means:
• Average equipped subracks
• Most common mixture of modules.
In other respects, such as technical data, and so on please refer to separate documentation:
Individual power supply units Data sheets included in Appendix A, Hardware Modules
Voltage regulator units 6,2+DUGZDUH5HIHUHQFH0DQXDO
3RZHU6XSSO\,QWHUUXSWLRQ
≤10 ms
1
Unaffected operation
>10 ms
1
Safety shutdown.
At battery supply, the Advant Controller is equipped with an energy reservoir to comply
with this specification.
3URFHVV,QWHUIDFH
*HQHUDO7HFKQLFDO'DWD&DSDFLW\
(YHQW+DQGOLQJ
For each object type, there is a buffer in the controller for event bursts. These buffers have the
following capacity:
7DEOH (VWLPDWHG6\VWHP3RZHU&RQVXPSWLRQ
&RQWUROOHUDQG
QXPEHURI,2VXEUDFN
3RZHUFRQVXPSWLRQ
FRVϕ>DWDF
-- 240 W
1 420 W
3 780 W
5 1140 W
1. The time limit is valid at lowest permitted supply voltage 19.2 V and maximum load (worst
case)