Save the Program
Follow these steps to save your application program.
1. Choose File>Apply.
The program is saved temporarily in RSNetWorx for DeviceNet
software.
2. Exit the Logic Editor by choosing File>Exit.
3. Click OK on the Edit Device Parameters dialog.
If you do not click OK or you click Cancel, none of your
program changes will be saved. Any programming saved
temporarily using File>Apply is deleted.
4. Choose Save or Save As from the RSNetWorx for DeviceNet main
dialog.
Update the Program
If the I/O tags of safety slaves that configure the SmartGuard
controller’s local I/O are changed, you must start the Logic Editor and
check the program.
If you load the parameters to the controller without starting the Logic
Editor, a download error occurs in the Logic Editor because of data
inconsistency. If this error occurs, start the Logic Editor and check the
program, making any necessary modifications.