SRX3600 Services Gateway Environmental Specifications
Table 14 on page 64 specifies the environmental specifications required for normal services gateway
operation. In addition, the site should be as dust-free as possible. For more information, see “Site Preparation
Checklist for the SRX3600 Services Gateway” on page 65 and “Routine Maintenance Procedures for the
SRX3600 Services Gateway” on page 168.
Table 14: SRX3600 Services Gateway Environmental Specifications
ValueDescription
No performance degradation to 10,000 ft (3048 m)Altitude
Normal operation ensured in relative humidity range of 5% to 90%,
noncondensing
Relative humidity
Normal operation ensured in temperature range of 32°F (0°C) to 104°F (40°C)
Nonoperating storage temperature in shipping carton: –40°F (–40°C) to
158°F (70°C)
Temperature
Tested to meet Telcordia Technologies Zone 4 earthquake requirementsSeismic
AC power: 5845 BTU/hour (1714 W)
DC power: 6223 BTU/hour (1825 W)
Maximum thermal output
NOTE: Install the services gateway only in restricted areas, such as dedicated equipment rooms
and equipment closets, in accordance with Articles 110-16, 110-17, and 110-18 of the National
Electrical Code, ANSI/NFPA 70.