EasyManuals Logo

ABB REC650 User Manual

ABB REC650
656 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #192 background imageLoading...
Page #192 background image
Voltage
START
START
TRIP
Start
&
Trip
Output
Logic
Time integrator
Definite Time Delay
TimeDlyOperate
TimeDlyReset
Comparator
U < IntBlockLevel
BLOCK
en05000735.vsd
Frequency Comparator
f > StartFrequency
TRIP
BLKDMAGN
BLOCK
OR
BLKTRIP
IEC05000735 V1 EN
Figure 83: Schematic design of overfrequency protection SAPTOF
8.2.8 Technical data
Table 144: SAPTOF technical data
Function
Range or value Accuracy
Operate value, start function (35.00-75.00) Hz ± 2.0 mHz at
symmetrical three-
phase voltage
Reset ratio
>0.999 -
Operate time, start function At 50 Hz: 200 ms typically at f
set
-0.5 Hz to f
set
+0.5 Hz
At 60 Hz: 170 ms typically at f
set
-0.5 Hz to f
set
+0.5 Hz
-
Reset time, start function At 50 and 60 Hz: 55 ms typically at f
set
+0.5 Hz
to f
set
-0.5 Hz
-
Timer (0.000-60.000)s <250 ms
8.3 Rate-of-change frequency protection SAPFRC
Section 8 1MRK 511 287-UEN A
Frequency protection
186
Technical manual

Table of Contents

Other manuals for ABB REC650

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REC650 and is the answer not in the manual?

ABB REC650 Specifications

General IconGeneral
BrandABB
ModelREC650
CategoryControl Unit
LanguageEnglish

Related product manuals