12.16.3 Function block
SSIMG
BLOCK
BLK_ALM
PRESSURE
TEMP
PRES_ALM
PRES_LO
SET_P_LO
SET_T_LO
RESET_LO
PRESSURE
PRES_ALM
PRES_LO
TEMP
TEMP_ALM
TEMP_LO
IEC09000129-1-en.vsd
IEC09000129 V1 EN
Figure 228: SSIMG function block
12.16.4 Signals
Inputs PRESSURE and TEMP together with settings PressAlmLimit,
PressLOLimit, TempAlarmLimit and TempLOLimit are not supported
in this release of 650 series.
Table 419: SSIMG Input signals
Name
Type Default Description
BLOCK BOOLEAN 0 Block of function
BLK_ALM BOOLEAN 0 Block all the alarms
PRESSURE REAL 0.0 Pressure input from CB
TEMP REAL 0.0 Temperature of the insulation medium from CB
PRES_ALM BOOLEAN 0 Pressure alarm signal
PRES_LO BOOLEAN 0 Pressure lockout signal
SET_P_LO BOOLEAN 0 Set pressure lockout
SET_T_LO BOOLEAN 0 Set temperature lockout
RESET_LO BOOLEAN 0 Reset pressure and temperature lockout
Table 420: SSIMG Output signals
Name
Type Description
PRESSURE REAL Pressure service value
PRES_ALM BOOLEAN Pressure below alarm level
PRES_LO BOOLEAN Pressure below lockout level
TEMP REAL Temperature of the insulation medium
TEMP_ALM BOOLEAN Temperature above alarm level
TEMP_LO BOOLEAN Temperature above lockout level
Section 12 1MRK 511 287-UEN A
Monitoring
484
Technical manual