Section 15 Basic IED functions
15.1 Self supervision with internal event list
15.1.1 Functionality
The Self supervision with internal event list INTERRSIG and SELFSUPEVLST
function reacts to internal system events generated by the different built-in self-
supervision elements. The internal events are saved in an internal event list presented
on the LHMI and in PCM600 event viewer tool.
15.1.2 Internal error signals INTERRSIG
15.1.2.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Internal error signal INTERRSIG - -
15.1.2.2 Function block
INTERRSIG
FAIL
WARNING
TSYNCERR
RTCERR
STUPBLK
IEC09000334-2-en.vsd
IEC09000334 V2 EN
Figure 262: INTERRSIG function block
15.1.2.3 Signals
Table 486: INTERRSIG Output signals
Name
Type Description
FAIL BOOLEAN Internal fail
WARNING BOOLEAN Internal warning
TSYNCERR BOOLEAN Time synchronization error
RTCERR BOOLEAN Real time clock error
STUPBLK BOOLEAN Application startup block
1MRK 511 287-UEN A Section 15
Basic IED functions
543
Technical manual

Table of Contents

Other manuals for ABB REC650

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REC650 and is the answer not in the manual?

ABB REC650 Specifications

General IconGeneral
BrandABB
ModelREC650
CategoryControl Unit
LanguageEnglish

Related product manuals