EasyManuals Logo
Home>Hitachi>Controller>PSC-A1T

Hitachi PSC-A1T Technical Catalogue

Hitachi PSC-A1T
774 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #147 background imageLoading...
Page #147 background image
4 Individual remote controls
PC-ART
TCGB0106 rev.0 - 12/2014
131
4
4.2.6.2 Optional functions list
Items
Optional Func-
tion
Indi-
vidual
Setting
Setting
Condi-
tion
Contents
b1
Removal of
Heating Tem-
perature Com-
pensation
00
Standard (Set
Temp. +4 ºC)
01
Removal (Set
Temp.)
02
Set Temp. +2 ºC
(*1)
b2
Circulator
Function at
Heating
Thermo-OFF
00 Not Available
01 Available
b3
3 Minutes OFF
Guard Com-
pressor
00
01
Not Available
Available
b4
Period for
Filter Sign
00 Standard
01 100 hours
02 1,200 hours
03 2,500 hours
04 No Indication
b5
Fixing of Op-
eration Mode
×
00 Not Available
01 Available
b6
Fixing of Set-
ting Tempera-
ture
×
00 Not Available
01 Available
b7
Fixing Cooling
Operation
×
00 Not Available
01 Available
b8
Automatic
COOL/HEAT
Operation
×
00 Not Available
01 Available
b9
Fixing Fan
Speed
×
00 Not Available
01 Available
bA
Not Prepared ×
“- -”
Fixed
Not Used
bb
Cooling Tem-
perature Com-
pensation
00
Standard (No
Compensation)
01 Set Temp. –1 ºC
02 Set Temp. –2 ºC
bC
Not Prepared -
00 Not Used
01
(Use as 00 condi-
tions)
bd
Not Prepared -
00 Not Used
01
(Use as 00 condi-
tions)
bE
Not Prepared -
00 Not Used
01
(Use as 00 condi-
tions)
C1
Not Prepared -
00 Not Used
01
(Use as 00 condi-
tions)
C2
Not Prepared -
“- -”
Fixed
Not Used
Items
Optional Func-
tion
Indi-
vidual
Setting
Setting
Condi-
tion
Contents
C3
Not Prepared
00 Not Used
01
(Use as 00 condi-
tions)
C4
Drain pump in
heating mode
00 Not available
01 Available
C5
Static pressure
selection (RPI)
00
Average static
pressure (factory
set)
01
High static pres-
sure
02
Low static pres-
sure
Increased Fan
Speed (RCI,
RCIM, RCD)
00 Normal
01 Speed increase 1
02 Speed increase 2
C6
Increasing Fan
Speed
00 Not Available
01 Available
C7
Cancelling 3
Minutes Com-
pressor Guard.
00 Available
01 Available
C8
Thermistor of
Remote Con-
trol Switch
00
Control by Indoor
Suction Thermis-
tor
01
Control by Ther-
mistor of Remote
Control Switch
02
Control by Aver-
age Value of
Indoor Suction
Thermistor and
Thermistor of
Remote Control
Switch
C9
Not Prepared -
“- -”
Fixed
Not Used
CA
Not Prepared -
“- -”
Fixed
Not Used
Cb
Selection of
Forced Stop-
page Logic
×
00
Forced Stoppage
Input: A Contact
01
Forced Stoppage
Input: B Contact
CC
Not Prepared ×
00 Not Used
01
(Use as 00 condi-
tions)
Cd
Not Prepared
00 Not Used
01
(Use as 00 condi-
tions)
CE
Not Prepared -
00 Not Used
01
(Use as 00 condi-
tions)

Table of Contents

Other manuals for Hitachi PSC-A1T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi PSC-A1T and is the answer not in the manual?

Hitachi PSC-A1T Specifications

General IconGeneral
BrandHitachi
ModelPSC-A1T
CategoryController
LanguageEnglish

Related product manuals