7: Services
SLC™ 8000 Advanced Console Manager User Guide 109
2. To save, click the Apply button.
Date and Time Commands
The following CLI commands correspond to the web page entries described above.
To set the local date, time, and local time zone (one parameter at a time):
set datetime <one parameter>
Parameters
date <MMDDYYhhmm[ss]>
timezone <Time Zone>
Note: If you do not know a valid <Time Zone>, enter 'timezone <invalid time zone>' and
you will be guided through selecting one from the available time zones.
To view the local date, time, and time zone:
show datetime
To synchronize the SLC 8000 unit with a remote time server using NTP:
set ntp <one or more ntp parameters>
Parameters
localserver1 <IP Address or Hostname>
localserver2 <IP Address or Hostname>
localserver3 <IP Address or Hostname>
poll <local|public>
publicserver <IP Address or Hostname>
state <enable|disable>
sync <broadcast|poll>
To view NTP settings:
show ntp
Synchronize via Select one of the following:
Broadcast from NTP Server: Enables the SLC unit to accept time
information periodically transmitted by the NTP server. This is the default if
you enable NTP.
Poll NTP Server: Enables the SLC 8000 advanced console manager to query
the NTP Server for the correct time. If you select this option, complete one of
the following:
Local: Select this option if the NTP servers are on a local network, and
enter the IPv4 or IPv6 address of up to three NTP servers. This is the
default, and it is highly recommended.
Public: Select this option if you want to use a public NTP server, and select
the address of the NTP server from the drop-down list. This is not
recommended because of the high load on many public NTP servers. All
servers in the drop-down list are stratum-2 servers. (See www.ntp.org
for
more information.) Each public NTP server has its own usage rules --please
refer to the appropriate web site before using one. Our listing them here is
to provide easy configuration but does not indicate any permission for use.

Table of Contents

Other manuals for Lantronix SLC 8000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lantronix SLC 8000 and is the answer not in the manual?

Lantronix SLC 8000 Specifications

General IconGeneral
Rack mountingYes
Console portRJ-45
Serial ports quantity48
USB 2.0 ports quantity2
AC input voltage120-230 V
Power source typeAC
AC input frequency50 - 60 Hz
Weight and Dimensions IconWeight and Dimensions
Weight5030 g
Dimensions (WxDxH)436.9 x 304.8 x 43.18 mm

Related product manuals