Setpoint
Undertemp.
warning
Undertemperature warning
2 °C
D
Setpoint
Overtemp.
warning
Overtemperature warning [1]
2 °C
Setpoint
Overtemperature warning [2]
235 °C
455 °F
2 °C
D
Troubleshooting
6-7
P/N 7105144G
2008 Nordson Corporation
VersaBlue_NW
Undertemperature and Overtemperature − Warning −
Alarm Triggered
Alarm Reset
Undertemperature Warning Triggered
The temperature has fallen below the setpoint by more than the differential
value (D) Undertemperature warning delta for longer than 5 seconds.
Automatic Reset
The temperature has increased to 2 °C (3.6 °F) below the setpoint.
Overtemperature Warning Triggered
[1] The temperature has exceeded the setpoint by more than the differential
value (D) Overtemperature warning delta for longer than 5 seconds.
or
[2] 235 °C (455 °F) was exceeded for longer than 5 seconds.
Automatic Reset
The temperature has fallen to 2 °C (3.6 °F) above the setpoint.