System description
SIMOCODE pro
1-98 GWA 4NEB 631 6050-22 DS 03
Delta networks:
1
)
Table 1-21: Decoupling module requirements for delta networks
Single-phase networks:
Table 1-22: Decoupling module requirements for single-phase networks
1) Mainly in North America
Delta networks Network configuration Decoupling
module
required
Note
3-wire, delta
single-phase grounded
Yes Parameter
"Voltage display
-> Line to line
voltage" must be
activated.
3-wire, delta
insulated
Yes Parameter
"Voltage display
-> Line to line
voltage" must be
activated.
Center tap grounded Yes Parameter
"Voltage display
-> Line to line
voltage" must be
activated.
Single-phase networks Yes Parameter "Voltage
display -> phase
voltages" must be
active.
The applied voltage
can be calculated as
follows
U_L1N + U_L2N.