Technical data
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 03
D-17
D.5.4 Technical data of the DM-F PROFIsafe digital module
LED display
DM-F PROFIsafe
Color Meaning
"READY" OFF System interface disconnected/supply voltage too
low/device defective
Green Device is ready for operation/system interface OK
Flashing
green
Device is ready for operation/system interface is
inactive or faulty
"DEVICE" OFF Supply voltage too low
Green Device is ready for operation
Red Device is defective or interrupted
"OUT" OFF Safety-oriented output inactive
Green Safety-oriented output active
Flashing
green
Feedback circuit not closed when starting condition
has been fulfilled
"GF" OFF No general fault
Red General fault (PROFIsafe inactive, incorrect PROFIsafe
address, wiring fault, device defective)
"1" Yellow PROFIsafe address 1
"2" Yellow PROFIsafe address 2
"3" Yellow PROFIsafe address 4
"4" Yellow PROFIsafe address 8
"5" Yellow PROFIsafe address 16
"6" Yellow PROFIsafe address 32
"7" Yellow PROFIsafe address 64
"8" Yellow PROFIsafe address 128
"9" Yellow PROFIsafe address 256
"10" Yellow PROFIsafe address 512
DIP switch Setting of the safety functions
SET/RESET button
•
Application of parameters set via DIP switch
•Resetting of faults (also possible via "TEST/RESET" onbasic unit)
Inputs (binary)
•3 inputs 24 V DC (83, 85, 89)
•Supply via terminal 84 or external supply
•Common connected, electrically isolated inputs for acquiring process-
signals (e.g., local control station, keyswitch, limit switch, etc.), fre-
elassignable to control functions