Technical data
SIMOCODE pro
D-16 GWA 4NEB 631 6050-22 DS 03
Table D-7: Technical data of the digital module DM-F Loca
Yellow Without start-up testing
Flashing
yellow
Configuration mode awaits confirmation
Flickering
yellow
Configuration fault
"8" OFF Automatic starting after power failure
Yellow No automatic starting after power failure
Flashing
yellow
Configuration mode awaits confirmation
Flickering
yellow
Configuration fault
DIP switch Setting of the safety functions
SET/RESETbutton
•Application of parameters set via DIP switch
•Resetting of faults (also possible via "TEST/RESET" on basic unit)
Inputs with safety relay
function
2 sensor inputs 24 V DC (Y12, Y22)
•Supply via terminal T1 or T2 with cross-circuit monitoring or external
supply without cross-circuit monitoring
•Functions parameterizable via DIP switch
1 start signal input 24 V DC (Y33)
•For monitored reconnection of the relay enabling circuits after a
safety-oriented disconnection
•Supply via terminal T2 or T3
1 cascading input 24 V DC (1)
•For use in connection with a higher-level safety relay
•Supply via terminal T2 or T3
1 feedback circuit input 24 V DC (Y34)
•For contactor monitoring of the motor and incoming supply
contactors via seriesconnected auxiliary switch normally-closed
contacts
•Supply via terminal T3
Cable length sensor
input and start signal
input (single)
1500 m
Input characteristic Type 2 according to EN 61131-2