Data formats and data records
SIMOCODE pro
B-20 GWA 4NEB 631 6050-22 DS 03
B.10 Data record 95 - Service data/statistical data
Writing the service data/statistical data
Writing is only possible if password protection is not active.
Additional abbreviations
r/w: value can be written/changed
r: value can only be read
1) Can only be written when the start monitoring function is active!
Byte.Bit Designation Type Range Unit Informa-
tion
0.0 Coordination Byte[4] BU1 BU2
4.0 Permissible starts - Actual value Byte 0 .. 255 r
1)
BU1 BU2
5.0 DM-F - Time until test required Byte 0 .. 255 1 week r BU2
6.0 Reserved Byte[2]
8.0 Number of parameterizations Word 0 .. 65535 r BU1 BU2
10.0 Number of overload trips Word 0 .. 65535 r/w BU1 BU2
12.0 Number of internal overload trips Word 0 .. 65535 r BU1 BU2
14.0 Motor stop time Word 0 .. 65535 1 h r/w BU1 BU2
16.0 Timer 1 - Actual value Word 0 .. 65535 100 ms r BU1 BU2
18.0 Timer 2 - Actual value Word 0 .. 65535 100 ms r BU1 BU2
20.0 Timer 3 - Actual value Word 0 .. 65535 100 ms r BU2
22.0 Timer 4 - Actual value Word 0 .. 65535 100 ms r BU2
24.0 Counter 1 - Actual value Word 0 .. 65535 r BU1 BU2
26.0 Counter 2 - Actual value Word 0 .. 65535 r BU1 BU2
28.0 Counter 3 - Actual value Word 0 .. 65535 r BU2
30.0 Counter 4 - Actual value Word 0 .. 65535 r BU2
32.0 Calculation module 1 - Output Word 0 .. 65535 r BU2
34.0 Calculation module 2 - Output Word 0 .. 65535 r BU2
36.0 Reserved Byte[4] 0
40.0 Motor operating hours D-word 0 .. 0xFFFFFFFF 1 s r/w BU1 BU2
44.0 Int. motor operating hours D-word 0 .. 0xFFFFFFFF 1 s r BU1 BU2
48.0 Device operating hours D-word 0 .. 0xFFFFFFFF 1 s r BU1 BU2
52.0 Number of starts D-word 0 .. 0xFFFFFFFF r/w BU1 BU2
56.0 Internal number of starts right D-word 0 .. 0xFFFFFFFF r BU1 BU2
60.0 Internal number of starts left D-word 0 .. 0xFFFFFFFF r BU1 BU2
64.0 Energy consumed D-word 0 .. 0xFFFFFFFF 1 kWh r/w UM
68.0 Reserved Byte[8]
Table B-11: Data record 95 - Diagnostics - Statistical data