Technical data
SIMOCODE pro
D-2 GWA 4NEB 631 6050-22 DS 03
D.1 Common technical data
Specifications EN 60204-1, EN 1760-1, DIN EN ISO 13849-1, IEC 61508
Test verification documents
Certificates:
www.siemens.com/industrial-controls/approvals.
Permiss. ambient temperature
In operation -25 °C - +60 °C
1)
For storage and transport -40 °C - +80 °C
2)
Site altitude above sea level
< 2000 m
<
3000 m Max. +50 °C (no safe isolation)
<
4000 m Max. +40 °C (no safe isolation)
Degree of protection
(according to IEC 60529)
All components (except current
measuring module with bus
connection, operator panel and door
adapter)
IP20
Current measuring module with
bus connection
IP00
Operator panel (front) and door
adapter (front) with cover
IP54
Shock resistance (sine pulse)
according to DIN EN 60068-2-27
15 g / 11 ms
Mounting position Any
Frequencies 50/60 Hz ± 5 %
EMC stability according to
•IEC 60947-1, IEC 60947-5-1,
SN 27095, NE21
•DM-F: IEC 61326-3-1
Corresponds to Degree of Severity 3
Conducted interference, burst
according to IEC 61000-4-4
2 kV (power ports)
overvoltage limiter is required
for inductive loads
.
1 kV (signal ports)
Conducted interference, high
frequency according to
IEC 61000-4-6
10 V
Conducted interference, surge
according to IEC 61000-4-5
2 kV (line to earth)
1 kV (line to line)
Electrostatic discharging,
ESD according to IEC 61000-4-2
8 kV (air discharge)
6 kV (contact discharge)
3)
Field-related interference according
to IEC 61000-4-3
10 V/m