Data formats and data records
SIMOCODE pro
B-8 GWA 4NEB 631 6050-22 DS 03
B.3 Data record 63 - Analog value recording
Table B-4: Data record 63 - Analog value recording
The unit of the measured value is dependent on the assigned analog value.
You will find all the available analog values with their units in Chapter A.4
"Socket assignment table - analog".
B.4 Data record 67 - Process image of the outputs
Byte.Bit Designation Type Range Information
0.0 StartPos Word 0 BU2
2.0 Channel No. Byte 1 BU2
3.0 Analog value record currently running Bit 0, 1 BU2
3.1 Trigger event occurred Bit 0, 1 BU2
3.2 Reserved Bit[6] 0
4.0 Measured value (0) Word 0 ... 65535 BU2
6.0 Measured value (1) Word 0 ... 65535 BU2
...
122.0 Measured value (59) Word 0 ... 65535 BU2
124.0 Reserved Byte[76] 0
Byte.Bit Designation Default
(also see parameters)
Type Information
0.0 Cyclic receive - Bit 0.0 Control station - PLC/PCS [DP] ON< Bit
BU1 BU2
0.1 Cyclic receive - Bit 0.1 Control station - PLC/PCS [DP] OFF Bit
0.2 Cyclic receive - Bit 0.2 Control station - PLC/PCS [DP] ON> Bit
0.3 Cyclic receive - Bit 0.3 Test 1 Bit
0.4 Cyclic receive - Bit 0.4 Motor protection - Emergency start Bit
0.5 Cyclic receive - Bit 0.5 Mode selector S1 Bit
0.6 Cyclic receive - Bit 0.6 Reset 1 Bit
0.7 Cyclic receive - Bit 0.7 Not assigned Bit
1.0 Cyclic receive - Bit 1.0 Not assigned Bit
1.1 Cyclic receive - Bit 1.1 Not assigned Bit
1.2 Cyclic receive - Bit 1.2 Not assigned Bit
1.3 Cyclic receive - Bit 1.3 Not assigned Bit
1.4 Cyclic receive - Bit 1.4 Not assigned Bit
1.5 Cyclic receive - Bit 1.5 Not assigned Bit
1.6 Cyclic receive - Bit 1.6 Not assigned Bit
1.7 Cyclic receive - Bit 1.7 Not assigned Bit
2.0 to 3.7 Cyclic receive - Analog value Not assigned Word BU2
Table B-5: Data record 67 - Process image of the outputs