Monitoring functions
SIMOCODE pro
5-6 GWA 4NEB 631 6050-22 DS 03
5.2.2 I> (upper limit)
Trip level, warning level
When monitoring current limits I> (upper limit), two different response levels
I> (upper limit) trip level, I> (upper limit) warning level can be parameterized
and monitored.
If the current of one or more phases exceeds the response level, current limit
monitoring responds.
Trip level and warning level activity
The trip level/warning level is only effective when the motor is running, the
start-up procedure has been completed and there is no test position
feedback (TPF) (run+).
Response at trip level
Here you can set how SIMOCODE pro should respond when the trip level is
overshot.
See also "Tables of responses of SIMOCODE pro" in Chapter "Important
information".
Table 5-3: "Warning level" response for monitoring current limits I>
Response at warning level
Here you can set how SIMOCODE pro should respond when the warning
level is overshot:
See also "Tables of responses of SIMOCODE pro" in Chapter "Important
information".
Table 5-4: "Warning level" response for monitoring current limits I>
Hysteresis
Here you can set the hysteresis for the current limits I> (upper limit):
Trip level: 0 to 1020% of I
s
in 4% increments
Warning level: 0 to 1020% of I
s
in 4% increments
Response Trip level
Deactivated X
Signaling X
Warning -
Tripping X
Delay 0 - 25.5 s (0.5 s
)
Response Warning level
Deactivated X
Signaling X
Warning X
Tripping -
Delay 0 - 25.5 s (0.5 s
)
Hysteresis 0 to 15% of the threshold value in 1% increments
Default: 5 %