Technical data
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 03
D-19
D.5.5 Technical data of the analog module
Mounting Snap-on mounting onto 35 mm standard mounting rails or
screw attachment via additional plug-in lugs
Display
•Green "READY" LED •Continuous light: "Ready for operation"
•Flashing: "No connection to basic unit"
System interfaces For connecting to a basic unit, an additional expansion
module, a current measuring module or a current/voltage
measuring module or the operator panel
Control circuit
Type of connection: 2-wire connection
Inputs:
•Channels 2 (passive)
•Parameterizable measuring
ranges
0/4 mA - 20 mA
•Cable shielding Recommended for up to 30 m and outside the switchgear
cabinet; shielding mandatory for cables over 30 m
•Max. input current
(destruction limit)
40 mA
•Accuracy ±1 %
•Input resistance 50 Ohm
•Conversion time 150 ms
•Resolution 12 bit
•Open circuit detection For measuring range 4 mA - 20 mA
•Isolation of the inputs to the
device electronics
No
Output:
•Channels 1
•Parameterizable output range 0/4 mA - 20 mA
•Cable shielding Recommended for up to 30 m and outside the switchgear
cabinet; shielding mandatory for cables over 30 m
•Max. output voltage 30 V DC
•Accuracy ±1 %
•Max. output load 500 Ohm
•Conversion time 25 ms
•Resolution 12 bit