Commissioning and service
SIMOCODE pro
14-16 GWA 4NEB 631 6050-22 DS 03
Example:
The most recent "Power - On" event was logged at a device operating time
of 17 days, 21 hours and 31 minutes. Therefore, at the moment of "Power -
On", the device was operating (supplied with voltage) for 17d 21h 31min.
The "No. of Starts >" fault was logged at a device operating time of 18 days,
22 hours, 17 minutes, i.e. 24 h 46 min after the most recent "Power - On".
When using a DM-F
, the events "Enabling circuit closed" and "Enabling circuit
open" are logged for the DM-F Local and/or the DM-F PROFIsafe in a
separate window:
•Time
• Event: "Enabling circuit closed" or "Enabling circuit open"
– Number:
Line 1: 200 or 202
Line 2: 201 or 203
–Text:
Line 1: "DM-F Local enabling circuit 0 -> 1" or DM-F PROFIsafe enabling
circuit 0 -> 1"
Line 2: "DM-F Local enabling circuit 1 -> 0" or "DM-F PROFIsafe enabling
circuit 1 -> 0".
The current DIP switch position of the DM-F Local and/or the DM-F
PROFIsafe is displayed under "DIP switch position DM-F during the last
event"
See also Chapter B.6 "Data record 72 - Error buffer".
14.5 Event buffer
In addition to the error buffer, various events can be stored in the event
buffer
Note:
From firmware version 3.0, the event buffer will be supported with the
following content from basic unit 2:
Entry 1 contains the last event "DM-F enabling circuit closed"
Entry 2 contains the last event "DM-F enabling circuit open"
See also Chapter B.7 "Data record 73 - Event memory".