Tables
SIMOCODE pro
A-12 GWA 4NEB 631 6050-22 DS 03
A.4 Socket assignment table - analog
This table contains all assignment numbers (No.) of the sockets (analog).
You only need these assignment numbers if you, for example, use a user
program to fill data records and write these back.
All inputs for analog data can only process values of type "Word" (2 bytes). In
order to also be able to process values of type "Byte", the following applies:
• The byte value is processed as a low byte, the high byte is always 0.
No. Designation Unit Information
0 Not connected BU1 BU2
1 Reserved
2 Reserved
3 Reserved
4 Timer 1 - Actual value 100 ms BU1 BU2
5 Timer 2 - Actual value 100 ms BU1 BU2
6 Timer 3 - Actual value 100 ms BU2
7 Timer 4 - Actual value 100 ms BU2
8 Counter 1 - Actual value BU1 BU2
9 Counter 2 - Actual value BU1 BU2
10 Counter 3 - Actual value BU2
11 Counter 4 - Actual value BU2
12 Reserved
13 Reserved
14 Reserved
15 Reserved
16 Max. current I_max 1 % / Is IM UM
17 Current I_L1 1 % / Is IM UM
18 Current I_L2 1 % / Is IM UM
19 Current I_L3 1 % / Is IM UM
20 Phase unbalance 1 % IM UM
21 Reserved
22 Reserved
23 Reserved
24 Voltage U_L1 1V UM
25 Voltage U_L2 1V UM
26 Voltage U_L3 1V UM
27 Cos phi 1% UM
28 Reserved
29 Reserved
30 Reserved
31 Reserved
32 Thermal motor model 2 % IM UM
33 Time to trip 100 ms IM UM
34 Recovery time 100 ms IM UM
Table A-4: Socket assignment table - analog