System description
SIMOCODE pro
1-20 GWA 4NEB 631 6050-22 DS 03
1.5.4 Communication
PROFIBUS DP
SIMOCODE pro has an integrated PROFIBUS DP interface (SUB-D socket or
terminal connection on the basic units).
SIMOCODE pro supports, for example, the following services:
Detailed description: See Chapter 12 "Communication".
1.5.5 Standard functions
Standard functions are pre-defined functions that can be easily activated,
e.g. time-staggered restart of the drives after a power failure.
SIMOCODE pro has the following standard functions:
Table 1-4: Standard functions
Detailed description: See Chapter 10 "Standard functions".
SIMOCODE
Service pro C (BU1) pro V (BU2)
Baud rates up to 12 MBit/s ✓ ✓
Automatic baud rate recognition ✓ ✓
Cyclic services (DPV0) and
acyclic services (DPV1)
✓ ✓
Operation as DPV1 slave downstream from the
Y link
✓ ✓
Alarms according to DPV1 ✓ ✓
Time synchronization via PROFIBUS DP — ✓
3UF50 compatibility mode — ✓
Safety-oriented tripping "PROFIsafe" — ✓
Table 1-3: PROFIBUS DP services
SIMOCODE
Standard function pro C (BU1)
Number
pro V (BU2)
Number
Test 2 2
Reset 3 3
Test Position Feedback (TPF) 1 1
External fault 4 6
Operational Protection OFF (OPO) — 1
Power Failure Monitoring (UVO) — 1
Emergency Start 1 1
Watchdog (PLC/PCS Monitoring) 1 1
Timestamping — 1
Safety-oriented Tripping "Local" — 1