Technical data
SIMOCODE pro
D-4 GWA 4NEB 631 6050-22 DS 03
D.2 Technical data of the basic units
Mounting Snap-on mounting onto 35 mm standard mounting rails or
screw attachment via additional plug-in lugs
Display
•Red/green/yellow "DEVICE" LED •Red: "Function test was negative, device is blocked"
•Green: "Ready for operation"
•Yellow: "Memory module or addressing plug detected"
•OFF: "No control supply voltage"
•Green "BUS" LED •Continuous light: "Communication with PLC/PCS"
•Flashing: "Baud rate recognized/communication with PC/
programming device"
•Red "GEN. FAULT" LED Continuous light/flashing: "Feeder fault", e.g. overload tripping
"TEST/RESET" button •Resetting the device after tripping
•Function test (system self-test)
•Operation of memory module, addressing plug
System interfaces
•Front For connecting an operator panel or expansion modules. The
memory module, addressing plug or a PC cable can also be
connected to the system interface for parameterization
purposes.
•Bottom For connecting a current measuring module or current/
voltage measuring module
PROFIBUS DP interface
•Interface design
•Connection system
RS485
9-pole SUB-D socket (12 MBit)
Terminals (1.5 MBit), connection cross section as per control
circuit
Connection of a PROFIBUS DP cable via terminal connection or
9-pole SUB-D socket.
Rated control supply voltage U
s
(according to DIN EN 61131-2)
110 V - 240 V AC/DC 50/60 Hz 24 V DC
Operating range 0.85 x Us - 1.1 x Us - 0.8 x Us - 1.2 x Us -
Power consumption
•Basic unit 1 (3UF7000) 7 VA/5 W 5 W
•Basic unit 2 (3UF7010)
(including two expansion modules
connected to basic unit 2)
10 VA 7 W 7 W
Rated insulation
voltage U
i
300 V (for Degree of Pollution 3)
Rated impulse withstand voltage
U
imp
4kV