Specification/
Control function
Control station Contactor control
Lamp control
QLE<<
(ON<<)
QLE<
(ON<)
QLA
(OFF)
QLE>
(ON>)
QLE>>
(ON>>)
Status information
ON<< ON< OFF ON> ON>> QE1 QE2 QE3 QE4 QE5 ON<< ON< OFF ON> ON>>
Overload 1),2) ----- - -Active- ------
Direct starter 1),2) - - OFF ON - ON - - - - - OFF ON -
Reversing starter 1),2) - LEFT OFF Right - Right LEFT - - - LEFT OFF Right -
Circuit breaker 1),2) - - OFF ON - ON
pulse
-OFF
pulse
- ---OFFON-
Star-delta
starter 2)
--OFFON-Star
contactor
Delta
contactor
Network
contactor
- ---OFFON-
Star-delta reversing
starter2)
LEFT OFF Right - Star
contactor
Delta
contactor
Right
Network
contactor
Left
Network
contactor
- LEFT OFF Right -
Dahlander 2) - - OFF Slow Fast Fast Slow Fast
star
contactor
- ---OFFSlowFast
Dahlander
reversing starter 2)
Left
fast
Left
slow
OFF Right
slow
Right
fast
Right
fast
Right
slow
Fast
star
contactor
Left
slow
Left
fast
Left
fast
Left
slow
OFF Right
slow
Right
fast
Pole-changing starter 2) - - OFF Slow Fast Fast Slow - - - - - OFF Slow Fast
Pole-changing
reversing starter 2)
Left
fast
Left
slow
OFF Right
slow
Right
fast
Right
fast
Right
slow
-L
eft
sl
ow
Left
fast
Left
fast
Left
slow
OFF Right
slow
Right
fast
Solenoid valve 2) - - CLOSED OPEN - OPEN - - - - - - CLOSED OPEN -
Positioner 1 2) - CLOSED STOP OPEN - OPEN CLOSED - - - - CLOSED STOP OPEN -
Positioner 2 2) - CLOSED STOP OPEN - OPEN CLOSED - - - - CLOSED STOP OPEN -
Positioner 3 2) - CLOSED STOP OPEN - OPEN CLOSED - - - - CLOSED STOP OPEN -
Positioner 4 2) - CLOSED STOP OPEN - OPEN CLOSED - - - - CLOSED STOP OPEN -
Positioner 5 2) - CLOSED STOP OPEN - OPEN CLOSED - - - - CLOSED STOP OPEN -
Soft starter 2) - - OFF ON - ON
Network
contactor
- Reset ON
command
---OFFON-
Soft starter
with reversing contactor 2)
- LEFT OFF Right - Right
Network
contactor
Left
Network
contactor
Reset ON
command
- - LEFT OFF Right -
1) Basic unit 1, SIMOCODE pro C
2) Basic unit 2, SIMOCODE pro V