EasyManuals Logo
Home>Siemens>Control Unit>SIMOCODE pro

Siemens SIMOCODE pro System Manual

Siemens SIMOCODE pro
694 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #118 background imageLoading...
Page #118 background image
System description
SIMOCODE pro
1-100 GWA 4NEB 631 6050-22 DS 03
Digital module (DM)
Digital modules allow the type and number of binary inputs and relay
outputs on basic unit 2 to be further increased, if required.
The following digital modules are available for basic unit 2:
Table 1-23: Versions of digital modules
A maximum of 2 digital modules can be connected to one basic unit 2. A
further 4 additional binary inputs and 2 additional binary outputs are
available. All versions can be combined with each other. SIMOCODE pro V
can thus be extended to a maximum of 12 binary inputs and
7 relay outputs.
In the case of the monostable version, the relay outputs open
after switching off/failure/interruption of the supply voltage. With the
bistable version, the switching state of the relay outputs remains intact
even after switching off/failure/interruption of the supply voltage.
If required, you can set a delay time for the digital module inputs (see
Chapter 7.4 "Digital module inputs").
Supplying the inputs: See Chapter 13.3 "Wiring".
Note
To implement some motor control functions, a further digital module is
required in addition to the relay outputs on basic unit 2.
Note
If two digital modules are being used, the digital module connected the
closest to the basic unit via the system interface will be identified as digital
module 1. The digital module that follows behind will be identified as digital
module 2. If one digital module is connected to the front side and another to
the lower system interface of the basic unit, the digital module on the front
system interface of the basic unit will always be identified as digital
module 1.
Inputs Supply Outputs
4 inputs 24 V DC, external 2 monostable relay
outputs
4 inputs 110 - 240 V AC/DC, external 2 monostable relay
outputs
4 inputs 24 V DC, external 2 bistable relay outputs
4 inputs 110 - 240 V AC/DC, external 2 bistable relay outputs

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals