System description
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 03
1-7
Device series
SIMOCODE pro can be subdivided into two device series:
• SIMOCODE pro C – a compact system for direct and reversing starters
and/or for controlling a circuit breaker (MCCB)
• SIMOCODE pro V – a variable system, which offers numerous functions in
addition to all of the SIMOCODE pro C functions.
For each feeder, every system comprises a basic unit and a separate current
measuring module. Both modules are connected to each other electronically
via the system interface, by means of a connecting cable, and can be
installed together as a unit (behind one another) or separately (side-by-side).
An operator panel can also be connected optionally via the second system
interface on the basic unit, and installed in the switchgear cabinet door. The
current measuring module and the operator panel are connected to the
basic unit via connecting cables, which also supply the power.
Besides the existing inputs and outputs present, additional inputs, outputs,
and functions can be added to basic unit 2 (SIMOCODE pro V) by means of
optional expansion modules.
All modules can be connected to each other via connecting cables.
Connecting cables are available in various lengths. The maximum distance
between modules (e.g. between basic unit and current measuring module)
is 2.5 m.
Additional control programs are integrated in SIMOCODE pro V for star-delta
starters,
Dahlanders, pole-changing starters, soft starters – each also possible
in combination with reversing starter – solenoid valves and positioners.
SIMOCODE pro V is also particularly versatile. Its functionality can be extended,
if required, for example:
– The number and type of binary inputs and outputs can be increased in stages
and adapted.
– A current/voltage measuring module can be used for additional voltage
measurement and for monitoring power-related measured values (power
management).
– A temperature module enables the evaluation of several analog temperature
sensors.
– An earth-fault detection system can be integrated together with a summation
current transformer.
– An analog module extends the system by additional analog inputs and
outputs, for example, for fill-level or flow-rate monitoring.
– In addition to the standard operator panel (OP), an operator panel with display
(OPD) is optionally available (basic unit 2 from version *E03*).
SIMOCODE pro C is upwards-compatible with SIMOCODE pro V. This
means both series can be used simultaneously in your plant, according to
requirements.
Both systems can be used simultaneously in a low voltage switchgear
system according to requirements without additional outlay.
The parameterization of SIMICODE pro C can be transferred without
problems. Removable terminals and terminal markings are identical for both
systems.

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals