Monitoring functions
SIMOCODE pro
GWA 4NEB 631 6050- 22 DS 03
5-17
Response when warning level 0/4-20 mA> (upper limit), 0/4-20 mA< (lower limit)
Here you can set how SIMOCODE pro should respond if the set warning
level is either undershot or overshot:
See also "Tables of responses of SIMOCODE pro" in Chapter "Important
information".
Table 5-14: "Warning level" response for 0/4-20 mA monitoring
Marking
The marking is stored in the device and allocated and displayed in the Faults/
Warnings online dialog. Optional marking for designating the signal, e.g. "0/
4-20>". Range: Up to 10 characters.
Hysteresis for 0/4-20 mA
Here you can set the fluctuation range for the analog signal:
Note
Monitoring of a second process variable via input 2 of the analog module
can be done, for example, by free limit monitors.
Response Warning level
Deactivated X
Signaling X
Warning X
Tripping -
Delay 0 - 25.5 s (0.5 s
)
Hysteresis for the analog signal 0 to 15% in 1% increments (5 %)