Commissioning and service
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 03
14-3
Notes on parameterizing
You can parameterize SIMOCODE pro as follows:
• With the memory module in which the parameters have already been saved
from a basic unit. The memory module is plugged into the system interface.
If the memory module is connected to the system interface and the supply
voltage returns to the basic unit, the basic unit will be automatically
parameterized by the memory module. The parameters can also be loaded
into the basic unit from the memory module by briefly pressing the Test/
Reset button.
• With the SIMOCODE ES software via the serial interface:
The PC/programming device is connected to the system interface with the
PC cable.
• With an automation system and/or SIMOCODE ES software via
PROFIBUS DP. For this, the PROFIBUS DP cable should be connected to the
PROFIBUS DP interface of the basic unit.
Commissioning options
There are two commissioning options:
1. Normal case: SIMOCODE pro has not yet been parameterized and still has
the factory settings:
When connected to PROFIBUS DP, the "Bus" LED flashes green when a DP
master is connected.
2. SIMOCODE pro has already been parameterized:
– The parameters have already been loaded into the basic unit.
– The parameters from a previous application still exist. Check whether
the parameters (e.g. the set current) apply to the new application.
Change these accordingly, if necessary.