System description
SIMOCODE pro
1-30 GWA 4NEB 631 6050-22 DS 03
Test/Reset button:
Enables the device to be reset after tripping or after a fault has occurred and
makes it possible to test the device/motor feeder with or without tripping
the contactor control. If a memory module or addressing plug is plugged in,
the PROFIBUS address can be parameterized or adopted via the Test/Reset
button.
For more information see Chapter 10.2 "Test/Reset", Chapter 14.2.2 and
Chapter 14.3.2.
System interfaces:
2 system interfaces for connecting
• A current measuring module
• An operator panel.
Basic unit 2 (BU2).
Basic unit 2 is the fundamental component of the SIMOCODE pro V device
series and is used in combination with a current measuring module or
current/voltage measuring module and optional operator panels.
The following motor control functions are supported:
• Overload relay
• Direct and reversing starters
• Star-delta starter, also with reversing starter
• Two speeds, motors with separate windings (pole-changing starters), also
with reversing starter
• 2 speeds, motors with separate Dahlander windings, also with reversing
starter
• Positioner control
• Solenoid valve control
• Circuit breaker control (MCCB)
• Soft starter control, also with reversing starter.
In contrast to basic unit 1, basic unit 2 offers the following expansion
options:
• Increased device functionality via various expansion modules according to
need
• Implementation of a current/voltage measuring module in place of a current
measuring module
• Additional inputs and outputs, as required.
• Use of an operator panel with display in place of a standard operator panel.
LEDs for device diagnostics (Device, Bus, Gen.Fault):
These LEDs on the front of the device are used for device and fault
diagnostics, and indicate the basic status:
• Of the device itself via the Device LED
• About PROFIBUS communication via the Bus LED
• About any motor feeder faults via the Gen. Fault LED
For more information see Chapter 14.2.3.