Data formats and data records
SIMOCODE pro
B-36 GWA 4NEB 631 6050-22 DS 03
1) Value range dependent on current range of the IM/UM and the conversion factor
76.0 Word parameters (33)
76.0 Analog module - Start value output Word 0 .. 65535 0 Value for
0/4mA
AM
78.0 Analog Module - End value output Word 0 .. 65535 27648 Value for 20
mA
AM
80.0 TM - Trip level T> Word 0 .. 65535 1 K 0 TM
82.0 TM - Warning level T> Word 0 .. 65535 1 K 0 TM
84.0 Limit monitor 1 - Limit Word 0 .. 65535 0 BU2
86.0 Limit monitor 2 - Limit Word 0 .. 65535 0 BU2
88.0 Limit monitor 3 - Limit Word 0 .. 65535 0 BU2
90.0 Limit monitor 4 - Limit Word 0 .. 65535 0 BU2
92.0 Timer 3 - Limit Word 0 .. 65535 100 ms 0 BU2
94.0 Timer 4 - Limit Word 0 .. 65535 100 ms 0 BU2
96.0 Counter 3 - Limit Word 0 .. 65535 0 BU2
98.0 Counter 4 - Limit Word 0 .. 65535 0 BU2
100.0 Change-over pause Word 0 .. 65535 10 ms 0
102.0 Analog value recording -
Sampling rate
Word 1 .. 50000 1 ms 100 BU2
104.0 I
s
1 conversion factor - Counter Word 0 .. 65535 0 BU2
106.0 I
s
2 conversion factor - Counter Word 0 .. 65535 0 BU2
108.0 D-word parameters (37)
108.0 Motor protection - Set current I
s
2 D-Word
1)
10 mA 0
112.0 Trip level P> D-word 0 .. 0xFFFFFFFF 1 W 0 UM
116.0 Warning level P> D-word 0 .. 0xFFFFFFFF 1 W 0 UM
120.0 Trip level P< D-word 0 .. 0xFFFFFFFF 1 W 0 UM
124.0 Warning level P< D-word 0 .. 0xFFFFFFFF 1 W 0 UM
128.0 Truth table 9
type 5I/2O - Output 1
Bit [32] 0 .. 1..1B 0 BU2
132.0 Truth table 9
type 5I/2O - Output 2
Bit [32] 0 .. 1..1B 0 BU2
136.0 Calculation module 2, offset D-word -0x80000000 ..
0x7FFFFFFF
0BU2
140.0 Calculation module 1, counter/
offset
D-word 2x
-32768..32767
0BU2
Byte.
Bit
Designation
(PRM group)
Type Range Unit De-
fault
Note Informa-
tion
Table B-14: Data record 132 - Extended device parameters 1 (Cont.)