Data formats and data records
SIMOCODE pro
B-54 GWA 4NEB 631 6050-22 DS 03
B.21.10 Pole-changing reversing starter
Table B-31: Assignment of cyclic receive/send data, pole-changing reversing starter
*) for SIMOCODE pro V, basic type 1 only
Cyclic receive data
Bit 0.0 Device parameters -> Motor control -> Control stations -> PLC/PCS [DP] -> ON >>
Bit 0.1 Device parameters -> Motor control -> Control stations -> PLC/PCS [DP] -> OFF
Bit 0.2 Device parameters -> Motor control -> Control stations -> PLC/PCS [DP] -> ON >
Bit 0.3 Further function blocks -> Standard functions - Test/Reset -> Test 1 - Input
Bit 0.4 Further function blocks -> Standard functions -> Emergency start -> Emergency start - Input
Bit 0.5 Device parameters -> Motor control -> Control stations -> Mode selector S1
Bit 0.6 Further function blocks -> Standard functions -> Test/Reset -> Reset 1 - Input
Bit 0.7 Not connected
Bit 1.0 Device parameters -> Motor control -> Control stations -> PLC/PCS [DP] -> ON <<
Bit 1.1 Not connected
Bit 1.2 Device parameters -> Motor control -> Control stations -> PLC/PCS [DP] -> ON <
Bit 1.3 Not connected
Bit 1.4 Not connected
Bit 1.5 Not connected
Bit 1.6 Not connected
Bit 1.7 Not connected
Byte 2/3 *) (analog value) Not connected
Cyclic send data
Bit 0.0 Status - ON >>
Bit 0.1 Status - OFF
Bit 0.2 Status - ON >
Bit 0.3 Event - Pre-warning overload (I>115 %)
Bit 0.4 Status - Change-over pause active
Bit 0.5 Status - Remote mode
Bit 0.6 Status - General fault
Bit 0.7 Status - General warning
Bit 1.0 Status - ON <<
Bit 1.1 Not connected
Bit 1.2 Status ON <
Bit 1.3 Status - Interlocking time active
Bit 1.4 Not connected
Bit 1.5 Not connected
Bit 1.6 Not connected
Bit 1.7 Not connected
Byte 2/3 (analog value) Maximum current I_max
Byte 4/5 *) (analog value) Not connected
Byte 6/7 *) (analog value) Not connected
Byte 8/9 *) (analog value) Not connected