GFK-1504K B-1
Relay Contact Ratings
Mechanical Rating
Relay contacts are rated for 10
7
operations.
Electrical Rating
The relay contact use in VersaMax modules meet Underwriters Laboratories’ Pilot Duty
Rating for Control Circuits. Contact life depends on type of load and current, as
summarized in the table below.
Maximum Current for Load TypeOperating
Voltage
Resistive Inductive *
Typical Contact
Life (operations)
24 to 125VAC
24 to 125VAC
24 to 125VAC
24 to 125VAC
2.0 Amp
1.5 Amp
0.8 Amp
0.35 Amp
1.00 Amp
0.20 Amp
0.10 Amp
300,000
100,000
500,000
1,000,000
250VAC
250VAC
250VAC
250VAC
2.0 Amp
1.0 Amp
0.6 Amp
0.15 Amp
1.00 Amp
180,000
30,000
500,000
1,000,000
5 to 31VDC
5 to 31VDC
5 to 31VDC
5 to 31VDC
2.0 Amp
1.1 Amp
0.7 Amp
0.70 Amp
2.00 Amp
0.25 Amp
0.10 Amp
200,000
50,000
500,000
1,000,000
32 to 125VDC 0.2 Amp not rated 300,000
Power Factor = 0.4 minimum for AC inductive loads
Time Constant – 7mS for DC inductive loads
Installing suitable suppression across inductive loads enhances reliability. For DC, a free-
wheeling diode provides suitable suppression. For AC, an R-C filter can be used.
Appendix
B
PDFsupply.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE VersaMax and is the answer not in the manual?

GE VersaMax Specifications

General IconGeneral
BrandGE
ModelVersaMax
CategoryController
LanguageEnglish

Related product manuals