8.4.4.6 Flying restart controller
For a quick commissioning, the calculaons and sengs are made automacally during the
opmisaon.
Details
The following parameter is only relevant for the ying restart circuit if an asynchronous motor
is controlled. In case of a sensorless control of a synchronous motor (SL-PSM) the parameter
has no meaning.
Parameter Name / value range / [default seng] Info
0x2BA1:003
(P718.03)
Flying restart circuit: Restart me
(Flying restart: Restart me)
1 ... [5911]* ... 60000 ms
* Default seng depending on the size.
Integraon me for controlling the ying restart circuit.
8.4.4.7 SLVC controller
For a quick commissioning, the calculaons and sengs are made automacally during the
opmisaon.
Precondions
The SLVC controller is only eecve in the motor control type "Sensorless vector control
(SLVC)".
Parameter Name / value range / [default seng] Info
0x2B40:001 Gain
0.0000 ... [0.2686]* ... 1000.0000 Hz/A
* Default seng depending on the size.
Gain of the SLVC-Q controller.
0x2B40:002 Reset me
1.0 ... [2.3]* ... 2000.0 ms
* Default seng depending on the size.
Reset me of the SLVC-Q controller.
Motor control
Opmisaon of the control loops
Motor controller sengs
152