9.1 General network sengs
Acvate network control
In order to be able to control the inverter via network, a trigger must be rst assigned in
0x2631:037 (P400.37) to the "Acvate network control" funcon.
This trigger can for instance be the constant value "TRUE" or a digital input.
If the assigned trigger is = TRUE, the motor can only be started via the network control
word (excepon: Jog operaon; see chapter "Start / stop motor" ^ 350).
In case of an acvated network control, the following funcons are sll acve:
0x2631:001 (P400.01): Enable inverter
0x2631:002 (P400.02): Run
0x2631:003 (P400.03): Acvate quick stop
0x2631:004 (P400.04): Reset fault
0x2631:005 (P400.05): Acvate DC braking
0x2631:010 (P400.10): Jog foward (CW)
0x2631:011 (P400.11): Jog reverse (CCW)
0x2631:012 (P400.12): Acvate keypad control
0x2631:037 (P400.37): Acvate network control
0x2631:043 (P400.43): Acvate fault 1
0x2631:044 (P400.44): Acvate fault 2
0x2631:054 (P400.54): Posion counter reset
All other funcons congurable via 0x2631:xx (P400.xx) are deacvated in case of network
control. 4Flexible I/O conguraon ^ 344
Network control word and status word
For establishing a simple network connecon, the inverter provides predened control and
status words for device prole CiA 402, AC drive prole as well as in LECOM format. For imple-
menng your own formats, the data words NetWordIN1 and NetWordOUT1 are available. By
means of data mapping to a network register, each of these words can be transferred as proc-
ess date via network.
Designaon Parameter Associated mapping
entry *
Further informaon
CiA: Controlword 0x6040 0x60400010
4Device prole CiA 402 ^ 192
CiA: Statusword 0x6041 (P780.00) 0x60410010
AC Drive control word 0x400B:001 (P592.01) 0x400B0110
4AC Drive Prole ^ 193
AC Drive status word 0x400C:001 (P593.01) 0x400C0110
LECOM control word 0x400B:002 (P592.02) 0x400B0210
4Lenze LECOM prole ^ 194
LECOM status word 0x400C:002 (P593.02) 0x400C0210
NetWordIN1 0x4008:001 (P590.01) 0x40080110 For implemenng an individual control word format.
The funcons that are to be triggered via bits 0 ... 15 of the NetWordIN1
data word are dened in 0x400E:001 (P505.01) ... 0x400E:016 (P505.16).
NetWordOUT1 0x400A:001 (P591.01) 0x400A0110 For implemenng an individual status word format.
The triggers for bits 0 ... 15 of the NetWordOUT1 data word are dened
in 0x2634:010 (P420.10) ... 0x2634:025 (P420.25).
* A mapping entry consists of index, subindex and data length in bits of the parameter to be mapped.
General informaon about the process of data mapping can be found in the chapter of the
same name for the corresponding network.
Conguring the network
General network sengs
173

Table of Contents

Other manuals for Lenze i510 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i510 Series and is the answer not in the manual?

Lenze i510 Series Specifications

General IconGeneral
Protection ClassIP20
Overload Capacity150% for 60 seconds
Enclosure RatingIP20
DimensionsVaries by model
WeightVaries by model
Control TypeV/f control, vector control
Communication InterfacesCANopen, Modbus RTU, EtherCAT, PROFIBUS, PROFINET
Ambient Temperature-10°C to +50°C
Braking ResistorOptional
SafetySTO (Safe Torque Off)
Protection FeaturesOvercurrent, overvoltage, undervoltage, overtemperature, short circuit
Output Voltage0 to input voltage
Input Voltage200-240 V, 380-480 V
Voltage Range200-240 V, 380-480 V
Frequency Range0 to 599 Hz