9.4.2 Node address seng
Each network node must be provided with a unique node address.
The parameters for addressing the device are described below.
Details
The node address can be set in 0x2301:001 (P510.01).
The seng that is acve when the inverter is switched on is the eecve seng.
The acve node address is shown in 0x2302:001 (P511.01).
Parameter Name / value range / [default seng] Info
0x2301:001
(P510.01)
CANopen sengs: Node ID
(CANopen se.: Node ID)
1 ... [1] ... 127
Seng of the node address.
A change in the node address will not be eecve unl a CAN Reset
Node is performed.
0x2302:001
(P511.01)
Acve CANopen sengs: Acve node ID
(CANopen diag.: Acve node ID)
Read only
Display of the acve node address.
0x2303
(P509.00)
CANopen switch posion
(CANopen switch)
Read only
Display of the DIP switch seng at the last mains power-on.
9.4.3 Baud rate seng
All network nodes must be set to the same baud rate.
The parameters for the baud rate of the device are described below.
Details
The baud rate can be set in 0x2301:002 (P510.02).
The seng that is acve when the inverter is switched on is the eecve seng.
The acve baud rate is displayed in 0x2302:002 (P511.02).
Parameter Name / value range / [default seng] Info
0x2301:002
(P510.02)
CANopen sengs: Baud rate
(CANopen se.: Baud rate)
Seng of the baud rate.
A change in the baud rate will not be eecve unl a CAN reset node
is performed.
0 Automac (from version 03.00)
1 20 kbps Seng of the baud rate.
A change in the baud rate will not be eecve unl a CAN reset node
is performed.
2 50 kbps
3 125 kbps
4 250 kbps
5 500 kbps
6 800 kbps
7 1 Mbps
0x2302:002
(P511.02)
Acve CANopen sengs: Acve baud rate
(CANopen diag.: Acve baud rate)
Read only
Display of the acve baud rate.
0 Automac (from version 03.00)
1 20 kbps
2 50 kbps
3 125 kbps
4 250 kbps
5 500 kbps
6 800 kbps
7 1 Mbps
Conguring the network
CANopen
Baud rate seng
205

Table of Contents

Other manuals for Lenze i510 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i510 Series and is the answer not in the manual?

Lenze i510 Series Specifications

General IconGeneral
Protection ClassIP20
Overload Capacity150% for 60 seconds
Enclosure RatingIP20
DimensionsVaries by model
WeightVaries by model
Control TypeV/f control, vector control
Communication InterfacesCANopen, Modbus RTU, EtherCAT, PROFIBUS, PROFINET
Ambient Temperature-10°C to +50°C
Braking ResistorOptional
SafetySTO (Safe Torque Off)
Protection FeaturesOvercurrent, overvoltage, undervoltage, overtemperature, short circuit
Output Voltage0 to input voltage
Input Voltage200-240 V, 380-480 V
Voltage Range200-240 V, 380-480 V
Frequency Range0 to 599 Hz