7.3 Selecon of setpoint source
The selected "setpoint source" serves to provide the inverter with its setpoint. The setpoint
source can be selected individually for each operang mode.
Possible setpoint sources are:
Analog inputs
Keypad
Network
Parameterisable setpoints (presets)
"Motor potenometer" funcon
"Sequencer" funcon
Details
For applicaons only requiring one setpoint it is sucient to dene the standard setpoint
source in the following parameters.
For applicaons requiring a change-over of the setpoint source during operaon, the func-
ons for setpoint change-over have to be congured accordingly. 4Setpoint change-over
^ 365
Parameter Name / value range / [default seng] Info
0x2860:001
(P201.01)
Frequency control: Default setpoint source
(Stnd. setpoints: Freq. setp. src.)
Selecon of the standard setpoint source for operang mode "MS:
Velocity mode".
The selected standard setpoint source is always acve in the operat-
ing mode 0x6060 (P301.00) = "MS: Velocity mode [-2]" when no set-
point change-over to another setpoint source via corresponding trig-
gers/funcons is acve.
4Setpoint change-over ^ 365
1 Keypad The setpoint is specied locally by the keypad.
Default seng: 0x2601:001 (P202.01)
Use the and navigaon keys to change the keypad setpoint
(also during running operaon).
2 Analog input 1 The setpoint is dened as analog signal via the analog input 1.
4Analog input 1 ^ 409
3 Analog input 2 The setpoint is dened as analog signal via the analog input 2.
4Analog input 2 ^ 413
5 Network The setpoint is dened as process data object via the network.
4Conguring the network ^ 172
11 Frequency preset 1 For the setpoint selecon, preset values can be parameterised and selec-
ted.
4Setpoint source of preset setpoints ^ 373
12 Frequency preset 2
13 Frequency preset 3
14 Frequency preset 4
15 Frequency preset 5
16 Frequency preset 6
17 Frequency preset 7
18 Frequency preset 8
19 Frequency preset 9
20 Frequency preset 10
21 Frequency preset 11
22 Frequency preset 12
23 Frequency preset 13
24 Frequency preset 14
25 Frequency preset 15
Basic seng
Selecon of setpoint source
98

Table of Contents

Other manuals for Lenze i510 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i510 Series and is the answer not in the manual?

Lenze i510 Series Specifications

General IconGeneral
BrandLenze
Modeli510 Series
CategoryInverter
LanguageEnglish

Related product manuals