EasyManuals Logo
Home>Lenze>Inverter>i510 Series

Lenze i510 Series Commissioning

Lenze i510 Series
487 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #20 background imageLoading...
Page #20 background image
4.2.1.2 Fusing and terminal data
Fuse data
Inverter I51AE125B
I51AE137B
I51AE125D
I51AE137D
I51AE155B
I51AE175B
I51AE155D
I51AE175D
Cable installaon in compliance with EN 60204-1
Installaon method B2
operaon without mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 10 10 16 16
Circuit breaker
Characteriscs B
Max. rated current A 10 10 16 16
operaon with mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 10 10 16 16
Circuit breaker
Characteriscs B
Max. rated current A 10 10 16 16
Earth-leakage circuit breaker
1-phase mains connecon ≥ 30 mA, type A or B
3-phase mains connecon - ≥ 30 mA, type B - ≥ 30 mA, type B
Fuse data
Inverter I51AE211B
I51AE215B
I51AE222B
I51AE211D
I51AE215D
I51AE222D
Cable installaon in compliance with EN 60204-1
Installaon method B2
operaon without mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 25 25
Circuit breaker
Characteriscs B
Max. rated current A 25 25
operaon with mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 25 25
Circuit breaker
Characteriscs B
Max. rated current A 25 25
Earth-leakage circuit breaker
1-phase mains connecon ≥ 30 mA, type A or B
3-phase mains connecon - ≥ 30 mA, type B
Electrical installaon
Mains connecon
1-phase mains connecon 230/240 V
20

Table of Contents

Other manuals for Lenze i510 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i510 Series and is the answer not in the manual?

Lenze i510 Series Specifications

General IconGeneral
BrandLenze
Modeli510 Series
CategoryInverter
LanguageEnglish

Related product manuals