9.5.10 Restart communicaon
The following parameter can be used to restart communicaon.
Details
A restart of communicaon is required aer changes of the interface conguraon (e. g. node
address and baud rate) in order that the changed sengs become eecve.
For restarng communicaon, there are two opons:
a)
Switch inverter o and on again.
b)
Set the selecon = "Restart with current values [1]" in 0x2320 (P508.00).
Parameter Name / value range / [default seng] Info
0x2320
(P508.00)
Modbus communicaon
(Modbus comm.)
1 = restart communicaon in order that changed sengs of the interface
conguraon become eecve.
0 No acon/no error
1 Restart with current values
9.5.11 Response me seng
Dene a minimum me delay between the recepon of a valid Modbus message and the
response of the inverter.
Especially at higher baud rates, dening a minimum me delay ensures the data exchange
between transmier (Modbus master) and receiver (e. g. inverter).
Parameter Name / value range / [default seng] Info
0x2321:004
(P510.04)
Modbus sengs: Minimum response me
(Modbus se.: Min. resp. me)
0 ... [0] ... 1000 ms
Conguring the network
Modbus RTU
Response me seng
235

Table of Contents

Other manuals for Lenze i510 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i510 Series and is the answer not in the manual?

Lenze i510 Series Specifications

General IconGeneral
Protection ClassIP20
Overload Capacity150% for 60 seconds
Enclosure RatingIP20
DimensionsVaries by model
WeightVaries by model
Control TypeV/f control, vector control
Communication InterfacesCANopen, Modbus RTU, EtherCAT, PROFIBUS, PROFINET
Ambient Temperature-10°C to +50°C
Braking ResistorOptional
SafetySTO (Safe Torque Off)
Protection FeaturesOvercurrent, overvoltage, undervoltage, overtemperature, short circuit
Output Voltage0 to input voltage
Input Voltage200-240 V, 380-480 V
Voltage Range200-240 V, 380-480 V
Frequency Range0 to 599 Hz