13.9 Funcons for parameter change-over
The inverter supports several parameter sets. The parameter set can be selected by means of
the "Select parameter set (bit 0)" and "Select parameter set (bit 1)" funcons.
DANGER!
Changed parameter sengs can become eecve immediately depending on the acvang
method set in 0x4046 (P755.00).
The possible consequence is an unexpected response of the motor sha while the inverter is
enabled.
If possible, only carry out parameter changes while the inverter is disabled.
Certain device commands or sengs which might cause a crical state of the drive behav-
iour can generally only be carried our when the inverter is inhibited.
Details
The "parameter change-over" funcon provides a change-over between four sets with dier-
ent parameter values for up to 32 freely selectable parameters. For details on the compilaon
of the parameters and seng of the value sets, see the chapter "Parameter change-over".
^ 292
A value set is selected in a binary-coded fashion via the triggers assigned to the two Select
parameter set (bit 0)" and " Select parameter set (bit 1)" funcons in compliance with the fol-
lowing truth table:
Select parameter set (bit 1)
0x2631:042 (P400.42)
Select parameter set (bit 0)
0x2631:041 (P400.41)
Selecon
FALSE FALSE Value set 1
FALSE TRUE Value set 2
TRUE FALSE Value set 3
TRUE TRUE Value set 4
Change-over is eected depending on the acvaon method selected in 0x4046 (P755.00)
when a state change of the selecon inputs takes place or via the trigger assigned to the
"Load parameter set" funcon.
Parameter Name / value range / [default seng] Info
0x2631:040
(P400.40)
Funcon list: Load parameter set
(Funcon list: Load param.set)
Seng can only be changed if the inverter is inhibi-
ted.
For further possible sengs, see parameter
0x2631:001 (P400.01). ^ 351
Assignment of a trigger for the "Load parameter set" funcon.
Trigger = FALSE-TRUE edge: parameter change-over to the value set
selected via "Select parameter set (bit 0)" and "Select parameter set (bit
1)".
Trigger = FALSE: no acon.
Notes:
The acvaon method for the "Parameter change-over" funcon can
be selected in 0x4046 (P755.00).
0 Not connected
0x2631:041
(P400.41)
Funcon list: Select parameter set (bit 0)
(Funcon list: Sel. paramset b0)
Seng can only be changed if the inverter is inhibi-
ted.
For further possible sengs, see parameter
0x2631:001 (P400.01). ^ 351
Assignment of a trigger for the "Select parameter set (bit 0)" funcon.
Selecon bit with the valency 2
0
for "Parameter change-over" funcon.
Trigger = FALSE: selecon bit = "0".
Trigger = TRUE: selecon bit = "1".
0 Not connected
0x2631:042
(P400.42)
Funcon list: Select parameter set (bit 1)
(Funcon list: Sel. paramset b1)
Seng can only be changed if the inverter is inhibi-
ted.
For further possible sengs, see parameter
0x2631:001 (P400.01). ^ 351
Assignment of a trigger for the "Select parameter set (bit 1)" funcon.
Selecon bit with the valency 2
1
for "Parameter change-over" funcon.
Trigger = FALSE: selecon bit = "0".
Trigger = TRUE: selecon bit = "1".
0 Not connected
Flexible I/O conguraon
Funcons for parameter change-over
393

Table of Contents

Other manuals for Lenze i510 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i510 Series and is the answer not in the manual?

Lenze i510 Series Specifications

General IconGeneral
Protection ClassIP20
Overload Capacity150% for 60 seconds
Enclosure RatingIP20
DimensionsVaries by model
WeightVaries by model
Control TypeV/f control, vector control
Communication InterfacesCANopen, Modbus RTU, EtherCAT, PROFIBUS, PROFINET
Ambient Temperature-10°C to +50°C
Braking ResistorOptional
SafetySTO (Safe Torque Off)
Protection FeaturesOvercurrent, overvoltage, undervoltage, overtemperature, short circuit
Output Voltage0 to input voltage
Input Voltage200-240 V, 380-480 V
Voltage Range200-240 V, 380-480 V
Frequency Range0 to 599 Hz