14 Technical data
14.1 Standards and operang condions
14.1.1 Protecon of persons and device protecon
Enclosure
IP20 EN 60529
Type 1 NEMA 250 Protecon against contact
Open type only in UL-approved systems
Insulaon resistance
Overvoltage category III EN 61800-5-1 0 … 2000 m a.m.s.l.
Overvoltage category II above 2000 m a.m.s.l.
Control circuit isolaon
Safe mains isolaon by double/reinforced
insulaon
EN 61800-5-1
Protecve measures against
Short circuit
earth fault Earth fault strength depends on the operang status
Motor overtemperature I²xt monitoring
Overvoltage
Motor stalling
Leakage current
> 3.5 mA AC, > 10 mA DC EN 61800-5-1 Observe regulaons and safety instrucons!
Starng current
≤ 3 x rated mains current
14.1.2 EMC data
Actuaon on public supply systems
Implement measures to limit the radio interfer-
ence to be expected:
The machine or plant manufacturer is responsible for compliance
with the requirements for the machine/plant!
< 1 kW: with mains choke EN 61000-3-2
> 1 kW at mains current ≤ 16 A: without addi-
onal measures
Mains current > 16 A: with mains choke or
mains lter, with dimensioning for rated
power. Rsce ≥ 120 is to be met.
EN 61000-3-12 RSCE: short-circuit power rao at the connecon point of the
machine/plant to the public network.
Noise emission
Category C2 EN 61800-3 Type-dependent, for motor cable lengths see rated data
Noise immunity
Meets requirement in compliance with EN 61800-3
14.1.3 Motor connecon
Requirements to the shielded motor cable
Capacitance per unit length
C-core-core/C-core-shield < 75/150 pF/m ≤ 2.5 mm² / AWG 14
C-core-core/C-core-shield < 150/300 pF/m ≥ 4 mm² / AWG 12
Electric strength
Uo/U = 0.6/1.0 kV Uo = r.m.s. value external conductor to PE
U = r.m.s. value external conductor/external conductorU ≥ 600 V UL
Technical data
Motor connecon
425