13.9.1 Example 1: Acvaon via command (only when disabled)
Acvaon method 0x4046 (P755.00) = "Via command (disable required) [0]":
•
Switches S3 and S4 serve to select the parameter set (see the following table).
•
Switch S2 acvates the change-over. Since the change-over is acvated with a rising edge,
a buon (normally-open contact) can be used instead of a switch.
•
Change-over is only possible if the motor is not started (switch S1 open).
Connecon plan funcon
GND
AI1
AI2
AO1
10V
24V
DI1
DI2
DI3
DI4
DI5
DO1
X3
S1 S2 S3 S4
Switch S1 Run
Switch S2 Load parameter set
Switches S3 ... S4 Parameter set selecon:
S3 S4
O O Parameter set 1
On O Parameter set 2
O On Parameter set 3
On On Parameter set 4
Parameter Name Seng for this example
0x2631:001 (P400.01) Enable inverter Constant TRUE [1]
0x2631:002 (P400.02) Run Digital input 1 [11]
0x2631:004 (P400.04) Reset fault Not connected [0]
0x2631:013 (P400.13) Reverse rotaonal direcon Not connected [0]
0x2631:018 (P400.18) Acvate preset (bit 0) Not connected [0]
0x2631:040 (P400.40) Load parameter set Digital input 2 [12]
0x2631:041 (P400.41) Select parameter set (bit 0) Digital input 3 [13]
0x2631:042 (P400.42) Select parameter set (bit 1) Digital input 4 [14]
0x2824 (P200.00) Control selecon Flexible I/O conguraon [0]
0x4046 (P755.00) Acvaon of parameter set Via command (disable required) [0]
t
t
t
t
t
t
t
t
t
t
t
1
2
3 4 3
Digital input 1 [11] Run
Digital input 4 [14]
Constant TRUE [1]
Digital input 3 [13]
Digital input 2 [12]
Mains voltage
Select par. set (bit 0)
Parameter set 4 active [111]
Parameter set 1 active [108]
Enable inverter
Parameter set 3 active [110]
Parameter set 2 active [109]
Output signals
Status signals
Active parameter set
Select par. set (bit 1)
Load parameter set
Input signals
FunctionTrigger
The status signals can be assigned to digital outputs. 4Conguraon of digital outputs ^ 415
①
The change-over is acvated with the "Load parameter set" funcon (FALSE/TRUE edge).
②
If the inverter is enabled and the motor is started, a change-over is not possible.
Flexible I/O conguraon
Funcons for parameter change-over
Example 1: Acvaon via command (only when disabled)
395