EasyManuals Logo

Lenze i510 Series Commissioning

Lenze i510 Series
487 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #373 background imageLoading...
Page #373 background image
13.3.5 Setpoint source of preset setpoints
The four funcons "Acvate preset (bit 0)" ... " Acvate preset (bit 3)" enable change-over of
the setpoint to a parameterisable setpoint (preset value).
Precondions
A setpoint change-over to the respecve preset is only eected if no setpoint source with a
higher priority has been selected. 4Priority of the setpoint sources ^ 367
Details
A preset is selected in a binary-coded fashion via the triggers assigned to the four funcons
"Acvate preset (bit 0)" ... " Acvate preset (bit 3)" in compliance with the following truth
table:
Acvate preset Selecon
Bit 3
0x2631:021
(P400.21)
Bit 2
0x2631:020
(P400.20)
Bit 1
0x2631:019
(P400.19)
Bit 0
0x2631:018
(P400.18)
Preset Frequency setpoint PID setpoint Torque setpoint
FALSE FALSE FALSE FALSE No preset selected
FALSE FALSE FALSE TRUE Preset 1 0x2911:001 (P450.01) 0x4022:001 (P451.01) 0x2912:001 (P452.01)
FALSE FALSE TRUE FALSE Preset 2 0x2911:002 (P450.02) 0x4022:002 (P451.02) 0x2912:002 (P452.02)
FALSE FALSE TRUE TRUE Preset 3 0x2911:003 (P450.03) 0x4022:003 (P451.03) 0x2912:003 (P452.03)
FALSE TRUE FALSE FALSE Preset 4 0x2911:004 (P450.04) 0x4022:004 (P451.04) 0x2912:004 (P452.04)
FALSE TRUE FALSE TRUE Preset 5 0x2911:005 (P450.05) 0x4022:005 (P451.05) 0x2912:005 (P452.05)
FALSE TRUE TRUE FALSE Preset 6 0x2911:006 (P450.06) 0x4022:006 (P451.06) 0x2912:006 (P452.06)
FALSE TRUE TRUE TRUE Preset 7 0x2911:007 (P450.07) 0x4022:007 (P451.07) 0x2912:007 (P452.07)
TRUE FALSE FALSE FALSE Preset 8 0x2911:008 (P450.08) 0x4022:008 (P451.08) 0x2912:008 (P452.08)
TRUE FALSE FALSE TRUE Preset 9 0x2911:009 (P450.09)
... ... ...
TRUE TRUE TRUE TRUE Preset 15 0x2911:015 (P450.15)
Notes:
The frequency setpoint preset 5 is also used for the "Jog foward (CW)" 0x2631:010
(P400.10) funcon.
The frequency setpoint preset 6 is also used for the "Jog reverse (CCW)" 0x2631:011
(P400.11) funcon.
Parameter Name / value range / [default seng] Info
0x2631:018
(P400.18)
Funcon list: Acvate preset (bit 0)
(Funcon list: Setp: Preset b0)
For further possible sengs, see parameter
0x2631:001 (P400.01). ^ 351
Assignment of a trigger for the "Acvate preset (bit 0)" funcon.
Selecon bit with the valency 20 for the bit-coded selecon and acva-
on of a parameterised setpoint (preset value).
Trigger = FALSE: selecon bit = "0".
Trigger = TRUE: selecon bit = "1".
14 Digital input 4
0x2631:019
(P400.19)
Funcon list: Acvate preset (bit 1)
(Funcon list: Setp: Preset b1)
For further possible sengs, see parameter
0x2631:001 (P400.01). ^ 351
Assignment of a trigger for the "Acvate preset (bit 1)" funcon.
Selecon bit with the valency 21 for the bit-coded selecon and acva-
on of a parameterised setpoint (preset value).
Trigger = FALSE: selecon bit = "0".
Trigger = TRUE: selecon bit = "1".
15 Digital input 5
0x2631:020
(P400.20)
Funcon list: Acvate preset (bit 2)
(Funcon list: Setp: Preset b2)
For further possible sengs, see parameter
0x2631:001 (P400.01). ^ 351
Assignment of a trigger for the "Acvate preset (bit 2)" funcon.
Selecon bit with the valency 22 for the bit-coded selecon and acva-
on of a parameterised setpoint (preset value).
Trigger = FALSE: selecon bit = "0".
Trigger = TRUE: selecon bit = "1".
0 Not connected
0x2631:021
(P400.21)
Funcon list: Acvate preset (bit 3)
(Funcon list: Setp: Preset b3)
For further possible sengs, see parameter
0x2631:001 (P400.01). ^ 351
Assignment of a trigger for the "Acvate preset (bit 3)" funcon.
Selecon bit with the valency 2
3
for the bit-coded selecon and acva-
on of a parameterised setpoint (preset value).
Trigger = FALSE: selecon bit = "0".
Trigger = TRUE: selecon bit = "1".
0 Not connected
Flexible I/O conguraon
Setpoint change-over
Setpoint source of preset setpoints
373

Table of Contents

Other manuals for Lenze i510 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i510 Series and is the answer not in the manual?

Lenze i510 Series Specifications

General IconGeneral
Protection ClassIP20
Overload Capacity150% for 60 seconds
Enclosure RatingIP20
DimensionsVaries by model
WeightVaries by model
Control TypeV/f control, vector control
Communication InterfacesCANopen, Modbus RTU, EtherCAT, PROFIBUS, PROFINET
Ambient Temperature-10°C to +50°C
Braking ResistorOptional
SafetySTO (Safe Torque Off)
Protection FeaturesOvercurrent, overvoltage, undervoltage, overtemperature, short circuit
Output Voltage0 to input voltage
Input Voltage200-240 V, 380-480 V
Voltage Range200-240 V, 380-480 V
Frequency Range0 to 599 Hz

Related product manuals