6-1
Data Initialization
6-1-1
Data Initialization
• The parameter initialization function restores changed parameters to the factory default settings.
• It can also clear the fault monitor data.
• When the inverter is newly set after restoring parameters to the factory default settings, execute pa-
rameter initialization with “1: Initialize all parameters” set to Data Initialization (3008Hex-04Hex).
• Note that previous settings cannot be reverted to once Data Initialization (3008Hex-04Hex) is set to
a value other than “0” to execute parameter initialization. After initialization ends, Data Initialization
(3008Hex-04Hex) returns to “0.”
Parameter No. Function name Data Default data Unit
3008Hex-04Hex Data Initialization
0: Disable
1: Initialize all parameters
2: Initialize motor 1 parameters
3: Initialize motor 2 parameters
4: Restore user defined data
5: Initialize all parameters (except I/O
and communications)
6: Reserved
7: Clear alarm history
8: Clear selection of favorite function
code
0 -
• During operation, initialization is not possible. Perform initialization after stopping inverter operation.
Also, do not enter a RUN command as the inverter might operate unintentionally during initialization.
Parameter Initialization (3008Hex-04Hex = 1)
• When “1: Initialize all parameters” is set to Data Initialization (3008Hex-04Hex), all parameters ex-
cluding the following are set to their default data (values at the time of shipment from the factory).
Main Circuit Capacitor Service Life Coefficient (Measurement V
alue) (3008Hex-2BHex)
Main Circuit Capacitor Service Life Coefficient (Initial Value) (3008Hex-30Hex)
Service Life of Main Circuit Capacitor Remaining Time (3008Hex-4EHex)
Cumulative Run Time of Cooling Fan (3008Hex-2CHex)
Cumulative Run Time of Capacitors on Printed Circuit Boards (3008Hex-31Hex)
1st Startup Count for Motor (3008Hex-2DHex)
2nd Startup Counter for Motor (3009Hex-35Hex)
1st Cumulative Motor Run Time (3008Hex-5FHex)
2nd Cumulative Motor Run Time (3009Hex-34Hex)
User Preference Dataset Protection Function Selection (3020Hex-5FHex)
Monitor Exclusive Parameters (M, W Parameters)
• Parameters are initialized even if they are protected by a password, and both passwords 1 and 2
are canceled. (Refer to 8-7-2 Password Function on page 8-66.)
6 Basic Settings
6-3
M1 Series EtherCAT Type User’s Manual (I670)
6-1 Data Initialization
6
6-1-1 Data Initialization