6-1
Data Initialization
6-1-1
Data Initialization
The parameter initialization function restores changed parameters to the factory default settings.
It can also clear the fault monitor data.
When the inverter is newly set after restoring parameters to the factory default settings, execute pa-
rameter initialization with “1: Initialize all parameters” set to Data Initialization (3008Hex-04Hex).
Note that previous settings cannot be reverted to once Data Initialization (3008Hex-04Hex) is set to
a value other than “0” to execute parameter initialization. After initialization ends, Data Initialization
(3008Hex-04Hex) returns to “0.”
Parameter No. Function name Data Default data Unit
3008Hex-04Hex Data Initialization
0: Disable
1: Initialize all parameters
2: Initialize motor 1 parameters
3: Initialize motor 2 parameters
4: Restore user defined data
5: Initialize all parameters (except I/O
and communications)
6: Reserved
7: Clear alarm history
8: Clear selection of favorite function
code
0 -
During operation, initialization is not possible. Perform initialization after stopping inverter operation.
Also, do not enter a RUN command as the inverter might operate unintentionally during initialization.
Parameter Initialization (3008Hex-04Hex = 1)
When “1: Initialize all parameters” is set to Data Initialization (3008Hex-04Hex), all parameters ex-
cluding the following are set to their default data (values at the time of shipment from the factory).
Main Circuit Capacitor Service Life Coefficient (Measurement V
alue) (3008Hex-2BHex)
Main Circuit Capacitor Service Life Coefficient (Initial Value) (3008Hex-30Hex)
Service Life of Main Circuit Capacitor Remaining Time (3008Hex-4EHex)
Cumulative Run Time of Cooling Fan (3008Hex-2CHex)
Cumulative Run Time of Capacitors on Printed Circuit Boards (3008Hex-31Hex)
1st Startup Count for Motor (3008Hex-2DHex)
2nd Startup Counter for Motor (3009Hex-35Hex)
1st Cumulative Motor Run Time (3008Hex-5FHex)
2nd Cumulative Motor Run Time (3009Hex-34Hex)
User Preference Dataset Protection Function Selection (3020Hex-5FHex)
Monitor Exclusive Parameters (M, W Parameters)
Parameters are initialized even if they are protected by a password, and both passwords 1 and 2
are canceled. (Refer to 8-7-2 Password Function on page 8-66.)
6 Basic Settings
6-3
M1 Series EtherCAT Type User’s Manual (I670)
6-1 Data Initialization
6
6-1-1 Data Initialization