If you click Cancel in the process of restoring data to the CPU module, the data is not completely restored.
The CPU module still performs the data restoration even if you click Cancel in the process of restoring a
backup file in the memory card. You can turn off the CPU module to stop the data restoration from being
performed. To prevent the CPU module from operating incorrectly, restore the CPU module to the factory
setting, or perform the data restoration again.
The restoration source or restoration destination may contain a password and an ID. The following table
describes the password and the ID process.
Data restoration Description
Memory card
PU module
a. The ID in the backup file must be the same as the ID in the CPU module;
otherwise the data is not restored.
b. If there is a PLC password in the CPU module, the password in the backup file
must be the same as the PLC password in the CPU module. Otherwise the
data is not restored.
c. If there is no PLC password in the CPU module, and there is a password in the
backup file, the system restores the data, and the password in the backup file
becomes the PLC password in the CPU.
Computer
ISPSoft project
The ID and the password in the backup file become the program ID and the
project password in the ISPSoft project.