DVP-ES3/EX3/SV3/SX3 Series Hardware and Operation Manual
2-28
2.3 Power Supply Module
2.3.1 General Specifications
DVPPS01 / DVPPS02 / DVPPS05
Model
DVPPS01 DVPPS02 DVPPS05
Supply voltage 100~240VAC (-15%~+10%), 50/60Hz
Output voltage 24VDC (±3%)
M
current
1A 2A 5A
Ripple & Noise Less than 100mV
p-p
@ full load
Less than 240mV
p-p
@ full load
Efficiency 78%~87% @ full load More than 88% @ full load
Overcurrent /
short circuit
protection
Auto recovery
Overvoltage /
overtemperature
protection
--
Overvoltage protection: When
the device is experiencing
overvoltage, power it off for 5
seconds and it will be back to
normal after powering
Overtemperature protection:
When the device is
experiencing overtemperature,
power it off for 5 seconds and
after the internal temperature is
below 85
o
C, powering it on
again.
Ground
The diameter of the ground should not be less than the diameters of the
cables connected to the terminals L and N. (When multiple PLCs are used at the same time, be
sure to ground each one separately.)
Weight 158 g 250 g 488 g