DVP-ES3/EX3/SV3/SX3 Series Hardware and Operation Manual
9-38
Error
Code
(HEX)
Description
Solutions
0119
Non-Listen only connection
establishment failed.
Check if the I/O connections are established in the system
configuration.
Check if the scanner I/O connections are functioning.
011C
The parameters of Transport
class and Trigger in the EDS
file are mismatched.
Check if the product information and the EDS file matched.
Reload the EDS file.
Contact the adapter manufacturer to obtain the correct EDS file.
011E
The direction in the EDS file is
mismatched.
011F
Output fixed / variable flag in
the EDS file is incorrect.
0120
Input fixed / variable flag in the
EDS file is incorrect.
0121
The output priority in the EDS
file is incorrect.
0122
The input priority in the EDS
file is incorrect.
0123
The output connection type in
the EDS file is incorrect.
0124
The input connection type in
the EDS file is incorrect.
0125
The output redundant
ownership in the EDS file is
incorrect.
0126
The configuration size in the
EDS file is incorrect.
Check if the product information and the EDS file matched.
Reload the EDS file.
Contact the adapter manufacturer to obtain the correct EDS file.
0127
Adapter input size is set
incorrectly.
Check the input size setting in the connection parameters.
Contact the adapter manufacturer to obtain the correct EDS file.
0128
Adapter output size is set
incorrectly.
Check the output size setting in the connection parameters.
Contact the adapter manufacturer to obtain the correct EDS file.